The Pantograph Disconnectors are single break and vertical reach type Disconnectors mounted on a post insulator operated through a operating rod insulator. The divided support Disconnectors are mounted directly on the structure. These types of Disconnectors permit the design of modern switchgear installations with minimum-space requirement. An attractive simple design and high reliability are the main advantage of S&S Disconnectors |
Technical Data
TECHNICAL DATA – Pantograph Disconnector |
||||||||||
|
36 |
72.5 |
123 |
145 |
170 |
245 |
300 |
362 |
420 |
|
LIGHTNING IMPULSE WITHSTAND VOLTAGE
|
kV |
170 |
325 |
550 |
650 |
750 |
1050 |
1050 |
1175 |
1425 |
POWER FREQUENCY WITHSTAND VOLTAGE
|
kV |
70 |
140 |
230 |
275 |
325 |
460 |
460 |
460 |
520 |
SWITCHING IMPULSE WITHSTAND VOLTAGE
|
kV |
- |
- |
- |
- |
- |
- |
850 |
950 |
1050 |
CURRENT AND SHORT CIRCUIT RATINGS |
UP TO 4000A, STC 50kA - 125 kAp |